Data record tests.transformer-turns-ratio.ieeec57-12-90.conditions
Verified 2026-10-24 Confidence: Medium
Clause 7.1 of IEEE C57.12.90-2021 runs the ratio test at rated or lower voltage and at rated or higher frequency, prefers single-phase excitation on three-phase units when each phase is accessible, and, where a wye neutral is inaccessible, creates a virtual neutral by shorting one phase with the connections of Figure 9.
| Step | Item | Detail |
|---|---|---|
| Source | IEEE C57.12.90-2021 | Licensed standard, clause 7.1.2, 7.1.3, 7.1.4 |
| Data record | tests.transformer-turns-ratio.ieeec57-12-90.conditions | Verified 2026-10-24 |
| Entry | Transformer Turns Ratio | No revisions |
- Subject
- Transformer Turns Ratio (Test methods)
- Kind
- Method fact
- Source
- IEEE C57.12.90-2021, clause 7.1.2, 7.1.3, 7.1.4, Test Code for Liquid-Immersed Distribution, Power and Regulating Transformers, IEEE.
History
| Date | Change |
|---|---|
| 2026-10-24 | created |
| 2026-10-24 | revised |
| 2026-10-24 | review_status unreviewed -> software_reviewed |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record tests.transformer-turns-ratio.ieeec57-12-90.conditions." Transformer Testing Reference. 2026-10-24. https://www.transformertestingreference.com/data/tests.transformer-turns-ratio.ieeec57-12-90.conditions/.
Transformer Testing Reference, Data record tests.transformer-turns-ratio.ieeec57-12-90.conditions (Oct. 24, 2026), https://www.transformertestingreference.com/data/tests.transformer-turns-ratio.ieeec57-12-90.conditions/.
@misc{etr-data-tests-transformer-turns-ratio-ieeec57-12-90-conditions,
title = {Data record tests.transformer-turns-ratio.ieeec57-12-90.conditions},
howpublished = {\url{https://www.transformertestingreference.com/data/tests.transformer-turns-ratio.ieeec57-12-90.conditions/}},
organization = {Transformer Testing Reference},
publisher = {Transformer Testing Reference},
year = {2026},
note = {last substantive change 2026-10-24}
}{{cite web |title=Data record tests.transformer-turns-ratio.ieeec57-12-90.conditions |website=Transformer Testing Reference |publisher=Transformer Testing Reference |url=https://www.transformertestingreference.com/data/tests.transformer-turns-ratio.ieeec57-12-90.conditions/ |date=2026-10-24 |access-date=}}