Data record tests.transformer-excitation-current.ieeec57-12-90.basis

Verified 2026-10-24 Confidence: High

Clause 8.5 of IEEE C57.12.90-2021 states excitation current relative to the energized winding's rated line current, uses the smallest kVA rating as the base on a unit that carries more than one cooling-class rating, and for a three-phase unit averages the magnitudes of the line currents recorded during the no-load loss test.

ProvenanceIEEE C57.12.90-2021 supports data record tests.transformer-excitation-current.ieeec57-12-90.basis, which is cited on the entry Transformer Excitation Current.SOURCEIEEE C57.12.90-2021IEEE C57.12.90-2021Licensed standard, clause 8.5DATA RECORDtests.transformer-excitation-current.ieeec57-12-90.basistests.transformer-excita..Verified 2026-10-24ENTRYTransformer Excitation CurrentTransformer Excitation C..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE C57.12.90-2021Licensed standard, clause 8.5
Data recordtests.transformer-excitation-current.ieeec57-12-90.basisVerified 2026-10-24
EntryTransformer Excitation CurrentNo revisions
Subject
Transformer Excitation Current (Test methods)
Kind
Method fact
Source
IEEE C57.12.90-2021, clause 8.5, Test Code for Liquid-Immersed Distribution, Power and Regulating Transformers, IEEE.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-24created
2026-10-24revised
2026-10-24review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.transformer-excitation-current.ieeec57-12-90.basis." Transformer Testing Reference. 2026-10-24. https://www.transformertestingreference.com/data/tests.transformer-excitation-current.ieeec57-12-90.basis/.